NFIN EARTH LEAKAGE CIRCUIT BREAKERS
|
 |
 |
|
NFIN 2P |
NFIN 4P |
|
APPLICATION:
-
The
Residual Current Device(RCD) NFIN is in conformity with the standards of
IEC 1008, VDE 0664, CEE27 and BS 4293.It can cut off the fault circuit immediately on the occasion of shock
hazard or earth leakage of trunk line.Thus it is suitable to avoid the
shock hazard and fire caused by earth leakage.NFIN RCD is mainly suitable for using in varieties of plants, enterprises,
buildings, constructions, commerce. Hotels and families, It can be used in
circuits up to single phase 240V,threephase 415V,50 or 60Hz.
|
|
Specification: |
|
Type |
NFIN25 |
NFIN40 |
NFIN63 |
NFIN100 |
|
Rated current In(A) |
25 |
40 |
63 |
100 |
|
Rated operating current for earth
leakage IΔn(A) |
0.03,0.1,0.3,0.5 |
0.1
0.3
0.5 |
|
Rated non-operating current for earth
leakage IΔn(A |
0.5IΔn
|
|
Voltage Un(V) |
240(220) 415(380) |
|
Pole |
2, 4 |
Main Technical Data
|
Operating time(seconds) |
IΔn |
2IΔn |
0.25A (or
5IΔn) |
| 0.2 |
0.1 |
0.04 |
Limited value of non-operating
current for balance load
or unbalance load |
2In |
In minimum value of rated
making and breaking capacity |
In=25 |
In=40 |
In=63 |
| 200 |
300 |
400 |
Rated conditional short
circuit current Inc(A) |
1500 |
2000 |
3000 |
|
Endurance(times) |
4000 |
|
|
|
|