NFIN EARTH LEAKAGE CIRCUIT BREAKERS

NFIN 2P NFIN 4P

APPLICATION:

  • The Residual Current Device(RCD) NFIN is in conformity with the standards of IEC 1008, VDE 0664, CEE27 and BS 4293.It can cut off the fault circuit immediately on the occasion of shock hazard or earth leakage of trunk line.Thus it is suitable to avoid the shock hazard and fire caused by earth leakage.NFIN RCD is mainly suitable for using in varieties of plants, enterprises, buildings, constructions, commerce. Hotels and families, It can be used in circuits up to single phase 240V,threephase 415V,50 or 60Hz.

Specification:
Type NFIN25 NFIN40 NFIN63 NFIN100
Rated current In(A) 25 40 63 100
Rated operating current for earth leakage IΔn(A) 0.03,0.1,0.3,0.5 0.1
0.3
0.5
Rated non-operating current for earth leakage IΔn(A 0.5IΔn
Voltage Un(V) 240(220) 415(380)
Pole 2, 4

Main Technical Data

Operating time(seconds) IΔn 2IΔn 0.25A (or 5IΔn)
0.2 0.1 0.04
Limited value of non-operating
current for balance load
or unbalance load
2In
In minimum value of rated
making and breaking capacity
In=25 In=40 In=63
200 300 400
Rated conditional short
circuit current Inc(A)
1500 2000 3000
Endurance(times) 4000